논문 해외 국제전문학술지(SCI급) Chilled water temperature set-point reset based on outdoor air temperature and its cooling energy performance in an office building
- 학술지 구분 국제전문학술지(SCI급)
- 게재년월 2022-03
- 저자명 최종민
- 학술지명 JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY
- 발행처명 KOREAN SOC MECHANICAL ENGINEERS
- 발행국가 해외
- 논문언어 외국어
- 전체저자수 6
논문 초록 (Abstract)
In this study, the cooling energy performance of two strategies for controlling ChWT (chilled water temperature) are compared: the conventional control strategy of constantly fixing ChWT and the OAT (outdoor air temperature) compensation control strategy that adjusts ChWT according to the changes in OAT. OAT compensation control strategy was modeled and realized based on Appendix G of ASHRAE Standard 90.1. It was confirmed that applying OAT compensation control strategy can significantly reduce chiller energy consumption, which accounts for the largest portion of total cooling energy consumption. It was found that the difference in total cooling energy consumption between applying the conventional control of constantly fixing ChWT to 6 degrees C and applying the OAT compensation control was approximately 8 % and 3 % during spring (March to May) and summer (June to August), respectively. Additionally, during the fall (September-November) period, about 7 % of total cooling energy consumption could be saved.