논문 해외 국제전문학술지(SCI급) EVALUATION OF THE IMPACTS OF HIGH STAGE REFRIGERANT CHARGE ON CASCADE
- 학술지 구분 국제전문학술지(SCI급)
- 게재년월 2015-07
- 저자명 최종민
- 학술지명 RENEWABLE ENERGY
- 발행처명 PERGAMON-ELSEVIER SCIENCE LTD
- 발행국가 해외
- 논문언어 외국어
- 전체저자수 2
논문 초록 (Abstract)
Heat pump systems offer economical alternatives for recovering heat from different sources for use in domestic and industrial refrigeration, space heating, and air conditioni ng. Some of these domestic and industrial applications require very low evaporatingtemperatures and ve ry high condensing temperatures which induce high compressor pressure ratios beyond the practical range forsingle-stage heat pump cycles. This challenge can be overcome by adopting cascade heat pum p cycles. In this study, a water-to-water cascade heat pump is tested to investigate the effects of high stage refrigerant charge amount on the performance in a steady state and heating mode operation. The temperature difference between the condensing temperature of the LS cycle and the evaporating t emperature of the HS cycle at cascade heat exchanger was increased by reducing the HS refrigerant char ge amount, while the heat transfer rate between HS and LS cycles decreased due to a decreasing of refrigerant flow rate. Finally, COP showed lower value at the undercharged condition than that at the fully charged condition. The slope of the capacity with a HS charge amount was much steeper at undercharged co nditions than that at overcharged conditions. For HS undercharged conditions, the heating capa city decreased greatly, because heat transfer rate from LS cycle to HS cycle reduced.